• 1
  • 2
Product Range
 
Fan Coil
Ceiling & Floor Fan Coil Units Series
Views:3308   Updated:2014/7/4 19:04:42


STRUCTURE

Beautiful Panels and frame are made from high grade plastic, pressure injection and right assemble.

HEAT EXCHANGER

The coil is made of hydrophilic aluminum finned copper tube, optimum FPI increasing heat transfer efficiency .The connections have brass header with female fittings and equipped with air vent ,pipe into the drain pan.

FAN

Centrifugal fan and direct drive motor. Each fan is statically and dynamically balanced to ensure quiet operation and optimum performance..

DRAIN TRAY

Drain tray is treated with polyester powder painting anti corrosion and well insulation anti condensate .

FILTER

Easy removed filter is made of polypropylene fabric, which is washable type.

FILTER

Remote controller is standard and offered.

OPTIONAL

1.Balancing valve   2.Two or three way Valve   3.Wired controller 

TECHNICAL DATA

Product Type

FCU-51Ce

FCU-68Ce

FCU-85Ce

FCU-102Ce

FCU-136Ce

FCU-170Ce

FCU-204Ce

FCU-238Ce

Air Flow

High

m3/h

510

680

850

1020

1360

1700

2040

2380

Middle

m3/h

418

558

697

836

1115

1394

1673

1952

Low

m3/h

255

340

425

510

680

850

1020

1190

Total cooling capacity

High

W

3120

4090

4920

6070

8210

9380

11800

12700

Middle

W

2819

3738

4350

5452

7469

8535

10495

11175

Low

W

2323

3010

3504

4384

6043

6889

8480

9270

Total heating capacity

High

W

5014

6738

7618

9760

13176

14812

18030

19700

Middle

W

4358

5652

6817

8254

11297

12880

15737

17052

Low

W

3710

4986

5637

7027

9486

10664

13161

13987

Fan motor Input power

 

W

50

65

70

110

130

150

185

190

Power  Supply

 

V/PH/Hz

220/1/50/60

Controlling method

 

 

remote controller

Noise

 

dB(A)

39

41

43

45

46

48

50

51

Water Flow

kg/h

536

703

846

1044

1412

1613

2029

2184

Water Resistence

kPa

14

16

18

22

25

39

44

44

water pipe connections

mm

ZG3/4"(DN20)

Draining pipe

mm

Rc3/4"(DN20)

Unit dimension (L×W×H)

net

mm

905×673

×243

905×673

×243

905×673

×243

1288×673

×243

1288×673

×243

1672×673

×243

1672×673

×243

1672×673

×243

packaging

mm

995×765

×311

995×765

×311

995×765

×311

13755×765

×311

1375×765

×311

1760×765

×311

1760×765

×311

1760×765

×311

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 27℃/WB 19.5℃ , water inlet/outlet temperature 7℃/ 12℃   

*Heating capacity is measured under the condition : Ambient temperature DB 21℃, water inlet temperature 60℃